Conventional Activated sludge process for a beginner
Conventional Activated sludge process
·
Conventional
biological treatment of wastewater under aerobic conditions includes activated
sludge process (ASP) and Trickling Filter. The ASP was developed in England in
1914. The activated sludge process consists of an aeration tank, where organic
matter is stabilized by the action of bacteria under aeration and a secondary
sedimentation tank (SST), where the biological cell mass is separated from the
effluent of aeration tank and the settle sludge is recycled partly to the
aeration tank and remaining is wasted (Figure 19.1). Recycling is necessary for
activated sludge process.
·
The
aeration conditions are achieved by the use of diffused or mechanical aeration.
Loading Rate: The organic matter
loading rate applied to the reactor is quantified as kg of BOD
applied per unit volume of the
reactor per day, called as volumetric loading rate, or kg of BOD
applied per day per unit mass of
microorganisms present in the reactor (i.e. in the aeration tank),
called as organic loading rate or
F/M. This can be calculated as stated below:
Vol.
= Volume of aeration Tank, m3
Quantity of Return Sludge: Usually solid concentration
of about 1500 to 3000 mg/L (MLVSS
80% of MLSS) is maintained for conventional ASP and
3000 to 6000 mg/L for completely
mixed ASP. Accordingly the quantity of return sludge
is determined to maintain this
concentration. The sludge return ratio is usually 20
to 50%. The F/M ratio is kept as 0.2 to 0.4
for conventional ASP and 0.2 to 0.6 for completely
mixed ASP.
Aeration
units can be classified as:
1) Diffused Air Units
2) Mechanical Aeration Units
3) Combined Mechanical and diffused air units.
1.
Diffused air aeration
·
In diffused air aeration,
compressed air is blown through diffusers.
·
The tanks of these units are
generally in the form of narrow rectangular channels. The air diffusers are
provided at the bottom of tank.
·
The air before passing through
diffusers must be passed through air filter to remove dirt. The required
pressure is maintained by means of air compressors.
Air
Supply:
·
Normally air is supplied under pressure of 0.55 to 0.7 kg/cm2.
·
The quantity of air supplied varies from 1.25 to 9.50 m3/m3 of
sewage depending on the strength of the sewage to be treated and degree of
treatment desired. The oxygen transfer capacity of the aerators depends on the
size of air bubbles, for fine bubble oxygen transfer capabilities of aeration
device is 0.7 to 1.4 kg O2/KW.h. For medium bubble it is 0.6 to 1.0 kg O2/KW.h,
and for coarse bubble it is 0.3 to 0.9 kg O2/KW.h.
Mechanical
Aeration Unit
·
The
main objective of mechanical aeration is to bring every time new surface of
wastewater in contact with air. In diffuse aeration only 5 to 12% of the total
quantity of the air compressed is utilized for oxidation and rest of the air is
provided for mixing. Hence, mechanical aeration was developed.
·
For
this surface aerators either fixed or floating type can be used (Figure 19.3).
·
The
rectangular aeration tanks are divided into square tank and each square section
is provided with one mixer. The impeller are so adjusted that when electric
motors starts, they suck the sewage from the centre, with or without tube
support, and throw it in the form of a thin spray over the surface of the
wastewater.
Types of Activated Sludge Process
1. Conventional
aeration
Ø In
conventional ASP the flow model in aeration tank is plug flow type. Both the influent
wastewater and recycled sludge enter at the head of the tank and are aerated
for about 5 to 6hours for sewage treatment (Figure 19.4).
Ø The
influent and recycled sludge are mixed by the action of the diffusers or
mechanical aerators. Rate of aeration is constant throughout the length of the
tank.
Ø During
the aeration period the adsorption, flocculation and oxidation of organic
matter takes place. The F/M ratio of 0.2 to 0.4 kg BOD/kg VSS.d and volumetric
loading rate of 0.3 to 0.6 kg BOD/m3.d
is used for designing this type of ASP.
Ø Lower mixed liquor suspended solids (MLSS)
concentration is maintained in the aeration tank of the order of 1500 to 3000
mg/L and mean cell residence time of 5 to 15 days is maintained. The hydraulic
retention time (HRT) of 4 to 8 h is required for sewage treatment. Higher HRT
may be required for treatment of industrial wastewater having higher BOD
concentration. The sludge recirculation ratio is generally in the range of 0.25
to 0.5.
2. Tapered Aeration
Ø In
plug flow type aeration tank BOD load is maximum at the inlet and it reduces as
wastewatermoves towards the effluent end. Hence, accordingly in tapered
aeration maximum air is appliedat the beginning and it is reduced in steps
towards end, hence it is called as tapered aeration (Figure 19.5).
Ø By
tapered aeration the efficiency of the aeration unit will be increased and it
will
also result in overall economy. The
F/M ratio and volumetric loading rate of 0.2 to 0.4 kg BOD/kg VSS.d and 0.3 to 0.6 kg
BOD/m3.d, respectively, are adopted in design.
Ø Other
design recommendation are mean cell residence time of 5 to 15 days, MLSS of
1500 to 3000 mg/L, HRT of 4 to 8 h and sludge recirculation ratio of 0.25 to
0.5.
Ø Although,
the design loading rates are similar to conventional ASP, tapered aeration
gives better performance.
19.3Tapered
aeration activated sludge process
3. Step aeration
Ø If the sewage is
added at more than one point along the aeration channel, the process is called
as step aeration (Figure 19.6). This will reduce the load on returned sludge.
The aeration is uniform throughout the tank.
Ø The F/M ratio and volumetric loading rate of
0.2 to 0.4 kg BOD/kg VSS.d and 0.6 to 1.0 kg BOD/m3.d,
respectively, are adopted in design. Other design recommendation are mean cell
residence time of 5 to 15 days, MLSS of 2000 to 3500 mg/L, HRT of 3 to 5 h and
sludge recirculation ratio of 0.25 to 0.75. In step aeration the design loading
rates are slightly higher than conventional ASP. Because of reduction of
organic load on the return sludge it gives better performance.
4. Completely mixed
Ø
In
this type of aeration tank completely mixed flow regime is used. The wastewater
is distributed along with return sludge uniformly from one side of the tank and
effluent is collected at other end of the tank (Figure 19.7). The F/M ratio of
0.2 to 0.6 kg BOD/kg VSS.d and volumetric loading of 0.8 to 2.0 kg BOD/m3.d is used for
designing this type of ASP. Higher mixed liquor suspended solids (MLSS) is maintained
in the aeration tank of the order of 3000 to 6000 mg/L and mean cell residence
time of 5 to 15 days is maintained.
Reaction
rate kinetics, Conventional Activated sludge process
Y
= yield coefficient i.e., fraction of substrate
converted to biomass, (g/m3 of
biomass) / (g/m3 of substrate).
The value of Y typically varies from 0.4 to 0.8 mg VSS/mg BOD (0.25 to
0.4 mg VSS/mg COD) in aerobic systems.
Sequencing
batch reactor (SBR)
Ø A
sequencing batch reactor (SBR) is used in small package plants and also for
centralized treatment of sewage. The SBR system consists of a single completely
mixed reactor in which all the steps of the activated sludge process occurs
(Figure 19.10). The reactor basin is filled within a short duration and then
aerated for a certain period of time. After the aeration cycle is complete, the
cells are allowed to settle for a duration of 0.5 h and effluent is decanted
from the top of the unit which takes about 0.5 h. Decanting of supernatant is
carried out by either fixed or floating decanter mechanism. When the decanting
cycle is complete, the reactor is again filled with raw sewage and the process
is repeated. An idle step occurs between the decant and the fill phases. The
time of idle step varies based on the influent flow rate and the operating
strategy.
Ø During
this phase, a small amount of activated sludge is wasted from the bottom of the
SBR basin. A large equalization basin is required in this process, since the
influent flow must be contained while the reactor is in the aerating cycle.
Ø This
process is popular because entire process uses one reactor basin. In areas
where there is a limited amount of space, treatment takes place in a single
basin instead of multiple basins, allowing for a smaller footprint. In the
effluent low total-suspended-solid values of less than 10 mg/L can be achieved
consistently through the use of effective decanters that eliminate the need for
a separate clarifier.
Ø The
treatment cycle can be adjusted to undergo aerobic, anaerobic and anoxic
conditions in order to achieve biological nutrient removal, including
nitrification, denitrification and some phosphorus removal.
Comments
Post a Comment